PKGBN-IV-450
450 kVA Diesel Genset
450 kVA
Prime rating
50 Hz
Frequency
Less than 75 dB(A) at 1 m
Noise
CPCB IV+
Emission
A 450 kVA CPCB IV+ diesel genset with a Baudouin 6M21G4D4/5 engine, in an acoustic canopy below 75 dB(A) at 1 m.
Key features
Baudouin 6M21G4D4/5 engine
6-cylinder, turbocharged, aftercooled, 550 bHp at 1,500 rpm, 12.54 L displacement. Electronic (ECU) governing.
Leroy-Somer LSA 46.3 L11 alternator
Brushless and self-excited, with Class H insulation and IP23 protection; voltage regulation ±0.5% (R250) or ±0.25% (D350).
Acoustic canopy below 75 dB(A) at 1 m
1.5 mm sheet steel, rockwool lining (96 kg/m³).
DEIF SGC 120 MKII controller
Automatic start and stop, run-hour and energy counters, and protections for over- and under-voltage, over-current, over-speed, lube oil pressure, coolant temperature and fuel theft.
Urea (DEF) tank for after-treatment
70 L urea tank for the CPCB IV+ exhaust after-treatment system.
990 L fuel tank
CRCA steel, non-removable, bunded tank.
Technical specifications
| Genset | |
|---|---|
| Prime rating (kVA / kWe) | 450 kVA / 360 kWe |
| Power factor | 0.8 |
| Phase and voltage | 3-phase, 415 V |
| Frequency | 50 Hz |
| Rated current per phase at 415 V (A) | 626 |
| Noise | Less than 75 dB(A) at 1 m |
| Emission norm | CPCB IV+ |
| Model code | PKGBN-IV-450 |

Why choose this set

Engineered for critical power
Single sets or synchronised multi-set systems at up to 11 kV, like the 4 × 1500 kVA, 11 kV plant at the JM Baxi container terminal.

Checked at the factory
Our engineers check sets in the assembly hall at Banda before they are dispatched to site.

Frames welded in-house
Base frames and canopy frames are welded by our own team at Banda, to our own drawings.
Not sure which rating you need?
Tell us your loads and an applications engineer will size the set.