650 kVA Diesel Genset, front view

PKGBN-IV-650

650 kVA Diesel Genset

  • 650 kVA

    Prime rating

  • 50 Hz

    Frequency

  • Less than 75 dB(A) at 1 m

    Noise

  • CPCB IV+

    Emission

A 650 kVA CPCB IV+ diesel genset with a Baudouin 6M33G2D4/5 engine, in an acoustic canopy below 75 dB(A) at 1 m.

Find a dealerDatasheet

Call +91 91752 22136WhatsApp

Key features

  • Baudouin 6M33G2D4/5 engine

    6-cylinder, turbocharged, aftercooled, 771 bHp at 1,500 rpm, 19.6 L displacement. Electronic (ECU) governing.

  • Acoustic canopy below 75 dB(A) at 1 m

    1.5 mm sheet steel, rockwool lining (96 kg/m³).

  • DEIF SGC 120 MKII controller

    Automatic start and stop, run-hour and energy counters, and protections for over- and under-voltage, over-current, over-speed, lube oil pressure, coolant temperature and fuel theft.

  • Urea (DEF) tank for after-treatment

    90 L × 2 urea tank for the CPCB IV+ exhaust after-treatment system.

  • 990 L fuel tank

    Runs about 10 hours at 75% load on a full tank (101.12 L/h). CRCA steel, removable, bunded tank.

Technical specifications

Genset
Prime rating (kVA / kWe)650 kVA / 520 kWe
Power factor0.8
Phase and voltage3-phase, 415 V
Frequency50 Hz
Rated current per phase at 415 V (A)904
NoiseLess than 75 dB(A) at 1 m
Emission normCPCB IV+
Model codePKGBN-IV-650
650 kVA Diesel Genset, side view
Overall length 6,800 mm, height 2,670 mm.

Why choose this set

  • Pai Kane gensets with exhaust stacks at the JM Baxi container terminal

    Engineered for critical power

    Single sets or synchronised multi-set systems at up to 11 kV, like the 4 × 1500 kVA, 11 kV plant at the JM Baxi container terminal.

  • Engineers inspecting a large Pai Kane genset at the factory

    Checked at the factory

    Our engineers check sets in the assembly hall at Banda before they are dispatched to site.

  • Welder at work on a genset frame at the Pai Kane plant

    Frames welded in-house

    Base frames and canopy frames are welded by our own team at Banda, to our own drawings.

Not sure which rating you need?

Tell us your loads and an applications engineer will size the set.